6 changes: 6 additions & 0 deletions src/xeto/ph.doc/Equips.md
Original file line number Diff line number Diff line change
Expand Up @@ -49,3 +49,9 @@ Here are examples for the proper tagging of equipment:
siteRef: @site
equipRef: @site.chillerPlant

# Points
The standardized points for equip are:

- [ph.points::EnableCmd]: command that permits or prohibits equip to operate
- [ph.points::RunCmd]: commands an equip to run or stop running
- [ph.points::RunSensor]: senses the on/off state of an equip
60 changes: 28 additions & 32 deletions src/xeto/ph.doc/Motors.md
Original file line number Diff line number Diff line change
Expand Up @@ -20,28 +20,27 @@ sub-components of a larger piece of equip that we nest via
the [ph::PhEntity.equipRef] tag.

# Points
The standardized points for motor control are:
Standardized points for equip are extended to motors as follows:

- [ph::PhEntity.run] [ph::PhEntity.cmd]: primary on/off command
- [ph::PhEntity.enable] [ph::PhEntity.cmd]: secondary on/off command
- [ph::PhEntity.run] [ph::PhEntity.sensor]: run status sensor
- [ph::PhEntity.enable] [ph::PhEntity.sensor]: enable status sensor
- [ph::PhEntity.alarm] [ph::PhEntity.sensor]: bolean alarm condition
- [ph.points::MotorEnableCmd]: command that permits or prohibits a motor to operate
- [ph.points::MotorRunCmd]: commands a motor to run or stop running
- [ph.points::MotorRunSensor]: senses the on/off state of a motor
- [ph::PhEntity.alarm] [ph::PhEntity.sensor]: boolean alarm condition

The primary on/off point of equipment is always modeled with the [ph::PhEntity.run] tag.
Paired with [ph::PhEntity.cmd] it models the on/off command point; paired with [ph::PhEntity.sensor] it
models the run status point. Many VFDs also include a secondary [ph::PhEntity.enable] point
that requires both `run` and `enable` to be commanded to true in order for the
equipment to be on. In all cases, `true` models the *on* state, and `false` models
the *off* state.
Permission from [ph.points::MotorEnableCmd] may be required for [ph.points::MotorRunCmd] to
take effect.

If the motor is driven by a variable frequency drive, then it should be tagged
with the [ph::PhEntity.vfd] marker. Points related to the drive speed control:
If the motor is driven by a Variable Frequency Drive (VFD), then it should be tagged
with the [ph::PhEntity.vfd] marker.

- [vfd speed](ph::VfdSpeed) [ph::PhEntity.cmd]: speed command as percentage where 0% is off, 100% if full speed
- [vfd freq](ph::VfdFreq) [ph::PhEntity.cmd]: speed command as a frequency in Hz
- [vfd speed](ph::VfdSpeed) [ph::PhEntity.sensor]: speed status as percentage where 0% is off, 100% if full speed
- [vfd freq](ph::VfdFreq) [ph::PhEntity.sensor]: speed status as frequency in Hz
Points related to motor speed control:

- [ph.points::MotorSpeedModulatingCmd]: command for modulating motor speed
- [ph.elec::VfdOutputElecAcFreqCmd]: command for a VFD's output AC electric frequency
- [ph.points::MotorSpeedModulatingSensor]: sensor for modulating motor speed
- [ph.elec::VfdOutputElecAcFreqSensor]: sensor for a VFD's output AC electric frequency

Modulating speed is defined as a percentage where 0% is off and 100% is full speed.

Many VFDs will also provide many of the same points as an electric meter.
Measurements such as electric demand, consumption, voltage, and current
Expand All @@ -54,20 +53,17 @@ However in many cases a simple fan in a terminal unit such as a [ph::PhEntity.va
is more easily modeled as just a [ph::PhEntity.point].

## Fan Points
In simple cases where the fan is just a command and/or feedback sensor,
then it is best to model it as a [ph::PhEntity.point].

If annotated as an output with the [ph::PhEntity.cmd] tag, then the point
models the command status of the fan:
- false (off) or true (on)
- variable speed is 0% (off) to 100% (full speed)

If annotated as an input with the [ph::PhEntity.sensor] tag, then the
point models a sensor used to verify the fan status:
- false indicates no air flow (off) or true indicates successful
airflow (fan is on)
- if numeric, the point is differential pressure across the fan
measured in "inH₂O" or "kPa"
Standardized points for motors are extended to fans as follows:

- [ph.points::FanEnableCmd]: command that permits or prohibits a fan to operate
- [ph.points::FanRunCmd]: commands a fan to run or stop running
- [ph.points::FanRunSensor]: senses the on/off state of a fan
- [ph.points::FanSpeedModulatingCmd]: command for modulating fan speed

Modulating speed is defined as a percentage where 0% is off and 100% is full speed.

Permission from [ph.points::FanEnableCmd] may be required for [ph.points::FanRunCmd] to
take effect.

## Fan Equips
When the fan motor is a VFD, it should be modeled as an [ph::PhEntity.equip] entity
Expand Down